DC-UPS for capacitors, primary : 24 V, secondary: 24 V, output: 3, energy: 1 kJ, dimensions: 92,5x60x116 mm, weight: 0.6 kg
Short descriptionThe buffered DC power supply of the C-TEC series includes ultra-capacitors as energy storage inside the housing. During normal operation this capacitor is charged from the system voltage (Ue). The connected DC consumers are supplied as well from the system voltage. In case of an interruption of the system voltage, the energy of the ultra-capacitor is released regulated. With a dc/dc converter the load is supplied from the capacitor until it is discharged. The backup time depends on the state of charge of the capacitor and the discharge current.
The power supply hast he following characteristics:
The TECControl software (optional) monitors permanently the mains. The C-TEC equalizes mains disturbances (blackout) or short time drops of the input voltage (brownout). In case of mains failures > 2 Sekunden the C-TEC signalizes the mains failure to the PC, which conducts a system shutdown after an adjustable time. Subsequently the C-TEC as well as the IPC are switched off. In case of mains return, the C-TEC releases the output voltage, so that the system is able to restart automatically. If the mains returns during the shut down procedure, the C-TEC separates nevertheless the PC supply for a short time, so that the PC can restart afterwards without error. With this function all mains failures can be handle without problems, even complete systems may be switched off only with the main switch and the C-TEC respectively the TECCONTROL take over the complete internal switch off routine of the system. So downtimes and damages because of an uncontrolled process stop are avoided. |
---|
Nominal input voltage |
24 V DC -15 % / 10 % |
Input voltage range |
20,4 V … 26,4 V DC |
Min. charging voltage |
23,7 V DC |
Nominal input current (at 24,0 V DC) C charged 3 A load |
3,1 A DC |
Output voltage in back-up operation |
23,0 V DC ±2 % |
Nominal output current Max |
3 A DC (at 0,94 kJ) |
Nominal output current at maximum energy |
2 A DC (at 1,0 kJ) |
Current limitation |
1,05 … 1,2 x INom |
Power loss at Uc > |
2,5 W |
Power loss at 100 % load and charge |
7 W (max. 60 seconds) |
Efficiency at Uc > |
>96% @ (Ue=24,0 V DC; Ua=22,9 V DC; Ia=INom) |
Internal device protection (internal) |
4 A (T) |
fusing DC-output circuit (external) |
3 A (T) |
Type of connection: input Ue |
Spring terminal max. 1,0 mm² |
Type of connection: output Ua |
Spring terminal max. 1,0 mm² |
Message contact (Ue-OK[1]) |
Message via USB |
Protective system |
IP20 u. EN 60529 |
Operational temperature |
-20 °C … 60 °C |
Storage temperature |
-20 °C … 60 °C |
Rel. humidity |
≤95% no condensation |
Max. mounting height (without load reduction) |
2000 m above sea level |
dimensions (HxWxD) |
92,5 mm, 60 mm, 116 mm |
weight |
0,6 Kg |
Fixation | Snap-on mounting for DIN top hat rail |
UL approvals | No |