DC-UPS for batteries, primary : 230 V, secondary : 48 V, output: 1.2 A, dimensions: 92,5x60x116 mm, weight: 0.55 kg
Short DescriptionThe battery buffered DC power supply of the series AKKUTEC is working according the stand-by parallel mode and ensures in connection with a lead-acid accumulator a safe continuous DC power supply in case of mains failure.
The power supply has the following features:
USB interface: with corresponding drivers and Schneider TECControl Software the message contacts can be controlled and a Shut-Down/Restart can be made
|
---|
Nominal input voltage | 115 ... 230 V AC +15 % -10% |
Nominal frequency | 47 ... 63 Hz |
Max. nominal input current | 0,84 A @ 115 V AC 0,42 A @ 230 V AC |
Max. charging current at 100% load | 0,1 A |
Nominal output voltage | 48 V DC |
Output voltage range (with temp.-sensor) | 39,6 V DC ... 55,6 V DC |
Output voltage range (without temp.-sensor) | 39,6 V DC ... 52,8 V DC |
Max. nominal output current |
1,1 A DC |
Charge end voltage with temp.-sensor @ 25° | 54 V |
Charge end voltage without temp.-sensor |
52,8 V DC ±0,4 % |
Efficiency | 87 % |
Battery type |
Pb-Akku, maintenance-free Pb- Akku maintenance-free (Option with changed characteristic) |
Buffer time | Depending on battery and load |
Degree of protection | IP 20 |
Operating temperature | 0 ... 40 °C |
Storage temperature | recommended 0 ... 50 °C, permittd 0 ... 50 °C |
Relative humidity | 95 % non-condensing |
Max. altitude (without derating) | 2000 a. s. l. |
Dimensions (H x W x D) | 92,5 mm x 60 mm x 116 mm |
Weight | 0,55 kg |
Fixation |
Snap-on mounting for DIN top hat rail |
Norms and Regulations | EN 50178 / EN 60950 |
UL approvals |
UL 508 C22.2 |