R-8AI-8DIDO is a mixed module with a dual 10/100 Mbps Ethernet port and a front Micro USB programming port. The tool is designed for flexible cabling needs, small installation spaces, high-density I/O applications with embedded Ethernet networking.
The R-8AI-8DIDO has 8 analog input and 8 digital channels. The module is equipped with isolation between inputs, outputs and other low voltage circuits equal to 1,5 kVac. The configuration can be done through dedicated software and a web server with HTML5 support. IP address, MAC address, and firmware version associated with the single module can be identified or configured on the LAN network through the SDD (Seneca Discovery Device) tool. R-8AI-8DIDO supports both ModBUS TCP-IP and RS485 serial communication with ModBUS RTU protocol.
The R-8AI-8DIDO can be connected in Ethernet daisy chain mode with fault-bypass to ensure an Ethernet connection even if a module in the chain fails. Digital signals can be duplicated on one or more modules in Peer to Peer mode (I/O mirror functionality). Another advanced function is the "ModBUS Passthrough" function, thanks to which the module can divert to RS485 the requests coming from Modbus TCP-IP acting, in fact, as a gateway.
Power Supply | 10..40 Vdc; 19..28 Vac |
Auxiliary voltage output | 12 Vdc / 40 mA |
Max Consumption | 3 W |
Max Isolation | 1.5 kVac |
Status Indicators | Power supply Input / Output status STS (IP address / DHCP) RX / TX (Receive / transmit data over RS485) Ethernet TRF / LNK (Transit packets / Ethernet connection) |
Protection Degree | IP20 |
Operating temperature | -25..+65°C |
Dimensions (WxHxD) | 106 x 90 x 32 mm |
Weight | 170 g |
Housing | Pc/ABS material self-extinguishing UL94-V0, black colour |
Connections | 3.5mm pitch terminals, Micro USB connector and double RJ45 connector |
Mounting | On DIN EN 60715 rail, wall-mounted / panel-mounted |
Programming | SENECA Studio Configurator, Integrated web server, DIP-switch |
Special Features | Double Ethernet Daisy Chain connection LAN fault bypass (the active connection between the two Ethernet ports of the device in case of power failure) Max 32 Peer to Peer Rules (I/O Mirror) - No need for Master Counters with frequency, TON, TOFF, Period measurement Modbus Passthrough (TCP-IP to RS485) IP, MAC, Firmware identification and configuration by SDD tool |
Data Memory | FeRAM for counters backup |
Interfaces | Nr.2 Ethernet ports (with LAN fault-bypass function) 100 baseT on RJ45 - 100 Mbps (TCP-IP) Nr.1 RS485 port on terminals M23-M24-M25 - 115.200 bps (RS485) Nr.1 Micro USB (programming) |
Protocols | ModBUS RTU, ModBUS TCP-IP, HTTP |
Cable for Ethernet communication between devices | CAT5 or CAT5e unshielded |
ModBUS Communication | Up to 64 nodes without repeater and max speed 115 kbps |
ANALOG INPUT CHANNELS | |
Number of Channels | 8 Analog |
Type and Range | Voltage: -30 V ÷ -30 V; -120m V ÷ +120 mV Current: -24 mA ÷ +24 mA Thermocouple: J, K, T, E, N, R, S, B, L Thermoresistor Pt100 on AI1: -200 °C ÷ +200 °C (only for cold junction comp.) |
DIGITAL INPUT/OUTPUT CHANNELS | |
Number of Channels | 8 Digital Inputs/Outputs |
Type and Range | Inputs = voltage: ON threshold: > 9 V; OFF threshold: < 4 V; Vmax: 24 V; Impedance: 9 kΩ Outputs = MOSFET, PNP; max. voltage/current: 0.2 A / 24 V |
STANDARD | |
Certifications | CE |
Homologations and Standards | EN61000-6-4, EN61000-6-2, EN61010-1 |