NA30

PHASE & RESIDUAL OVERCURRENT, GROUND DIRECTIONAL, THERMAL IMAGE,
RESIDUAL OVERVOLTAGE

meer details

prijs op aanvraag

NA30

The relay type NA30 is typically used in radial MV networks as feeder or power transformer protection:
• on long radial feeders in ungrounded or Petersen coil and/or high resistance grounded systems
• on the LV side of parallel connected transformers with any grounding
• as earth fault protection of parallel connected generators or generator-transformer unit on the same busbar
The relay complies with CEI-016 requirements.

Specifications

Key: standard optional alternative

Applications
• Feeder
• Generator
• Motor
• Transformer
Protection functions
• Pt100 thermometric probes (26)
• Thermal image (49)
• Phase overcurrent (50/51)
• Residual overcurrent (50N/51N)
• Residual overvoltage (59N)
• Ground directional overcurrent (67N)
• High impedance restricted earth fault (87NHIZ)
• Breaker failure (BF)
Monitoring and control functions
• CB diagnostic
• Cold Load Pickup (CLP)
• CTs monitoring (74CT)
• Digital Fault recording (DFR)
• Fault and event logging (SER & SFR)
• Logic selectivity
• Multiple setting profiles
• Programmable Logic Controller
• Second harmonic restraint
• Self-test
• Trip circuit supervision (74TCS)
Hardware
• 2 binary inputs + 6 output relays + 8 LEDs
• Auxiliary power supply 110-230 Vac/dc
• Auxiliary power supply 24-48 Vac/dc
• Flush, projecting, projecting, rack, with separate MMI
• Network module with Ethernet FX port (optical fiber)
• Network module with Ethernet TX port (copper RJ45) + RS485 port
• Nominal current 1/5 A selectable by DIP-switch
• RS485 port (unavailable with Ethernet FX port)
• Standard CT amperometric inputs 1/5 A
Communication
• Modbus RTU RS232 protocol
• Modbus RTU RS485 / IEC 870-5-103 / DNP3 protocol
• Modbus TCP/IP protocol (network board must be provided)

  • toepassing GENERATOR|TRANSFORMER|FEEDER|MOTOR|INTERFACE
  • ANSI protectie Residual overcurrent (50N/51N)|Pt100 thermometric probes (26)|Thermal image (49)|Ground directional overcurrent (67N)|Phase overcurrent (50/51)|Breaker failure (BF)|High impedance restricted earth fault (87NHIZ)|Residual overvoltage (59N)